Online Prefixes: Siemens Breakers 30
Prefixes for the new Siemens [formerely
ITE] circuit breakers listed in Aaker.com's online database. For each Prefix the following tables show the poles, amps, ac voltage and frame size for the Siemens [formerely ITE] circuit breakers in our online database. The AIC [Average Interrupting Capacity] is read in conjunction with the AC Voltages. For example, the "HFD" prefix for 3 pole breakers shows AICs of 100/65/25kA and AC Voltages of 240/480/600 vac. The AICs are read 100kA @ 240vac, 65kA @ 480vac and 25A @ 600vac. |
Prefix | Mount | Poles | Amps | Volts AC | AIC | Dimensions | ||||||
W x H x D | ||||||||||||
B | Bolt-on | 1 | 15-70 | 120/240 | 10/10 kA | 1.00 x 3.75 x 2.37 | ||||||
2 | 15-125 | 120/240 | 10/10 kA | 2.00 x 3.75 x 2.37 | ||||||||
3 | 15-100 | 240 | 10 kA | 3.00 x 3.75 x 2.37 | ||||||||
BF | Bolt-on | 1 | 15-30 | 120 | 10 kA | 1.00 x 3.75 x 2.37 | ||||||
2 | 15-60 | 120/240 | 10/10 kA | 2.00 x 3.75 x 2.37 | ||||||||
BQ | Lug-to-lug | 1 | 15-70 | 120/240 | 10/10 kA | 1.00 x 3.75 x 2.37 | ||||||
2 | 15-125 | 120/240 | 10/10 kA | 2.00 x 3.75 x 2.37 | ||||||||
3 | 15-100 | 240 | 10 kA | 3.00 x 3.75 x 2.37 | ||||||||
BQD | Bolt-on | 1 | 15-100 | 120/277 | 65/14 kA | 1.00 x 4.00 x 2.70 | ||||||
2 | 15-100 | 120/240/488Y | 65/65/14 kA | 2.00 x 4.00 x 2.70 | ||||||||
3 | 15-100 | 120/240/488Y | 65/65/14 kA | 3.00 x 4.00 x 2.70 | ||||||||
ED2 | Lug-to-lug | 1 | 15-100 | 120 | 10 kA | 1.00 x 6.35 x 3.92 | ||||||
2 | 15-100 | 240 | 10 kA | 2.00 x 6.35 x 3.92 | ||||||||
3 | 15-100 | 240 | 10 kA | 3.00 x 6.35 x 3.92 | ||||||||
ED4 | Lug-to-lug | 1 | 15-100 | 120/277 | 65/22 kA | 1.00 x 6.35 x 3.92 | ||||||
2 | 15-125 | 240/480 | 65/18 kA | 2.00 x 6.35 x 3.92 | ||||||||
3 | 15-125 | 240/480 | 65/18 kA | 3.00 x 6.35 x 3.92 | ||||||||
ED6 | Lug-to-lug | 1 | 15-100 | 347 | 30 kA | 1.00 x 6.35 x 3.92 | ||||||
2 | 15-100 | 240/480/600 | 65/25/18 kA | 2.00 x 6.35 x 3.92 | ||||||||
3 | 15-125 | 240/480/600 | 65/25/18 kA | 3.00 x 6.35 x 3.92 | ||||||||
ED6-A | Lug-to-lug | 3 | 1-125 | 600 | NA | 3.00 x 6.35 x 3.92 | ||||||
FD | Lug-to-lug | 2 | 70-250 | 240/480/600 | 65/25/18 kA | 4.50 x 9.50 x 4.00 | ||||||
3 | 70-250 | 240/480/600 | 65/25/18 kA | 4.50 x 9.50 x 4.00 | ||||||||
FXD | Lug-to-lug | 2 | 70-250 | 240/480/600 | 65/25/18 kA | 4.50 x 9.50 x 4.00 | ||||||
3 | 70-250 | 240/480/600 | 65/25/18 kA | 4.50 x 9.50 x 4.00 | ||||||||
FXD-A | Lug-to-lug | 3 | 150-250 | 600 | NA | 4.50 x 9.50 x 4.00 | ||||||
HED4 | Lug-to-lug | 1 | 15-100 | 120/277 | 100/65 kA | 1.00 x 6.35 x 3.92 | ||||||
2 | 15-125 | 240/480 | 100/42 kA | 2.00 x 6.35 x 3.92 | ||||||||
3 | 15-125 | 240/480 | 100/42 kA | 3.00 x 6.35 x 3.92 | ||||||||
HFD | Lug-to-lug | 2 | 70-250 | 240/480/600 | 100/65/25 kA | 4.50 x 9.50 x 4.00 | ||||||
3 | 70-250 | 240/480/600 | 100/65/25 kA | 4.50 x 9.50 x 4.00 | ||||||||
HJD | Lug-to-lug | 2 | 200-400 | 240/480/600 | 100/65/35 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 200-400 | 240/480/600 | 100/65/35 kA | 7.50 x 11.00 x 4.00 | ||||||||
HLD | Lug-to-lug | 2 | 250-600 | 240/480/600 | 100/65/35 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 250-600 | 240/480/600 | 100/65/35 kA | 7.50 x 11.00 x 4.00 | ||||||||
HMLD | Lug-to-lug | 2 | 500-800 | 240/480/600 | 100/65/50 kA | 7.50 x 16.00 x 4.50 | ||||||
3 | 500-800 | 240/480/600 | 100/65/50 kA | 7.50 x 16.00 x 4.50 | ||||||||
HMD | Lug-to-lug | 2 | 500-800 | 240/480/600 | 100/65/50 kA | 9.00 x 16.00 x 6.00 | ||||||
3 | 500-800 | 240/480/600 | 100/65/50 kA | 9.00 x 16.00 x 6.00 | ||||||||
HND | Lug-to-lug | 3 | 100-900 | 240/480/600 | 100/65/50 kA | 9.00 x 16.00 x 6.00 | ||||||
JD | Lug-to-lug | 2 | 200-400 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 200-400 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||||
JXD4 | Lug-to-lug | 2 | 200-400 | 240 | 65 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 200-400 | 240 | 65 kA | 7.50 x 11.00 x 4.00 | ||||||||
JXD6 | Lug-to-lug | 2 | 200-400 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 200-400 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||||
LD6 | Lug-to-lug | 2 | 250-600 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 250-600 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||||
LMD6 | Lug-to-lug | 2 | 500-800 | 240/480/600 | 65/50/25 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 500-800 | 240/480/600 | 65/50/25 kA | 7.50 x 11.00 x 4.00 | ||||||||
LXD6 | Lug-to-lug | 2 | 450-600 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||
3 | 450-600 | 240/480/600 | 65/35/25 kA | 7.50 x 11.00 x 4.00 | ||||||||
MD6 | Lug-to-lug | 2 | 500-800 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||
3 | 500-800 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||||
MXD6 | Lug-to-lug | 2 | 500-800 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||
3 | 500-800 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||||
ND6 | Lug-to-lug | 2 | 800-1200 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||
3 | 800-1200 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||||
NXD6 | Lug-to-lug | 2 | 900-1200 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||
3 | 900-1200 | 240/480/600 | 65/50/25 kA | 9.00 x 16.00 x 6.00 | ||||||||
QJ2 | Lug-to-lug | 2 | 60-225 | 240 | 10 kA | 3.00 x 7.00 x 2.34 | ||||||
3 | 60-225 | 240 | 10 kA | 3.00 x 7.00 x 2.34 | ||||||||
QJH | Lug-to-lug | 2 | 60-225 | 240 | 22 kA | 3.00 x 7.00 x 2.34 | ||||||
3 | 60-225 | 240 | 22 kA | 3.00 x 7.00 x 2.34 |